Tuesdak
TDR MEMBER
What i do know is that towards the rear of the compressor there is a bunch of dye visible when using a UV light. Blasting it with brake cleaner didnt dissolve it so im thinking it could be pretty old. Or I had one of those events that @petersonj mentioned in the first reply. Directly on the back of the compressor there is a bit of what looks like old oil. would have to scrub it off as its dry.
Using the UV light I see no signs of dye at the exit of the evaporator, around the accumulator or any of the fittings towards the back of the engine. Only near the compressor is where I can see dye.
So I obviously have a leak somewhere as the shop filled the system 1 month ago.
Quick and dirty test to see if you have a blend door problem or low on charge: feel the inlet and out pipes of the evaporator at the fire wall. They should both be cold and nearly the same temp of cold. If the outlet pipe (going to the accumulator) is warm your system is likely low on charge.
Old dye is easy to figure out. Look for dye on the Oil Filter as it gets painted with oil and dye from the relief valve opening at 450+ psig. Assuming you have changed the oil since the A/C work.
For 2003 and IMO other years: there isn't anything acted on in the ECM to kick out the compressor when the high side hits or goes over 450+ psig. Failed cooling fan, clogged radiator, slow to kick on cooling fan clutch, whatever. The A/C system overheats to the point the relief valve blows 1/2 the system charge out at the safety relief valve. These pickups did this even brand new so they don't need a reason you can fix to dump 1/2 the A/C charge out the safety high pressure relief valve. 500 psig and the word "Safety" don't really go together as nothing is safe at 450+ psig except it keeps the high side of the A/C system from exploding.
In depth.
https://www.turbodieselregister.com...rams-ecm-defect-opening-the-ac-relief.258779/
Although the advice is to treat this like other systems the only way to know the proper charge is to evac and recharge the system. These systems are a flooded evaporator meaning the charge is determined by filling up the evaporator with liquid R134A and adding ~1/4 to 1/2 LB extra liquid R134A into the accumulator. Gauges will not tell you how much is in the accumulator. Some of the extra is a leakage reserve. When the system gets low the accumulator no longer has liquid R134A in it. As the system gets lower the evaporator is no longer full of liquid 134A and the outlet piper becomes warmer than the cold inlet pipe. These systems actually blow colder when they are slightly low and just about to starve the compressor for oil. Our compressors are tough and live through this oil starvation better than some others that would quickly fail. Refrigerant carries oil and low refrigerant conditions leave the oil trapped in the evaporator.
The orifice tube frosts when the pressures are low and defrosts when the fan kicks on.
this cycle repeats twice in a 5 minute span.
Either the orifice tube is clogged with debris, again, or the system is extremely low. These systems can frost the entire line from the orifice tube to the evap and the evap to the accumulator... and the line clear down to the compressor under the right conditions.
Is the frost just at the orifice tube or does it go further all the way to the evaporator inlet? Is the blower on high?
Low side goes from 10 to 30 then drops when the fan kicks on.
Is this psig or F? Doesn't matter as it's below freezing either way. This reading alone is clear you have a problem. IMO low. Clogged orifice tube is possible...
What did they also replace when they said your orifice tube was clogged? Condenser (essentially the first big debris filter and debris collector in the refrigerant flow out of the compressor), compressor, accumulator and flush the system? Debris in the system comes from one of three things: Compressor failure, dryer material coming apart in the accumulator, or internal corrosion from a system running with a leak on the low side that sucks moisture into the system. PAG oil + moisture = corrosive acid.
Did you see the OT and verify it was in fact clogged? I would be asking what from and was it (symptom) source of debris cured. IMO it could look like a clogged orifice tube to a shop if the cooling fan isn't running as described as the defect these trucks have. Fan checks out and shop is scratching their heads wondering why the high side went high and blew the relief when charge is good and fan checks out.